Features
- Prevents damage to sensitive electrical equipment
- Offers machine to facility-wide protection
- Includes a single- and three-phase portfolio
- Provides up to five seconds of ride-through
- Protects against brief, complete voltage loss
- Environmentally friendly
Product Comparison
Bulletin | 1608N | 1608P | 1608M | ||
Type | MiniDySC | ProDySC | MegaDySC | ||
Amp Range | 2-6 Amp | 12-50 Amp | 25-50 Amp | 100/110 Amp | 400 – 2400 Amp |
Voltage Range | ± 10% | 208 – 480 VAC | |||
Mounting | DIN Rail Mount | Panel Mount | Panel Mount | Floor Mount | Floor Mount |
Phase / Wiring | Single Phase / L-L and L-N | Three Phase/ 3-Wire and 4-Wire | Three Phase/ 3-Wire and 4-Wire | ||
Ride Through | up to 5 seconds | ||||
Batteries | Not Required | ||||
Enclosure | NEMA Type 1 | ||||
Operating Temperature Range | 0…40 °C |
Certifications
- Bulletin 1608N MiniDySC 2-6 Amp models are UL recognized, all other MiniDySC and ProDySC models are UL Listed.
- UL Listed,
- UL Recognized
Certifications apply when product is marked. See our Product Certification site for Declarations of Conformity, certificates and other certification details.
Standards Compliance
- Exceeds SEMI F47 Standard